Plumbing Failure Analysis: Stress Corrosion Cracking of Yellow Brass

March 2, 2017 By Tom Read Leave a Comment

Introduction

A plumbing failure analysis was performed to determine why a cold water supply line to a bathroom sink had failed after only one year of service. The failed supply pipe was made of chrome plated yellow brass. Figure #1 is a photograph of the failed line. There is a large opening which was the primary crack; in addition, there was another small crack near the ferrule. It is believed that this ‘second’ crack opened up when the corrugated tube was removed from service. This pipe failure analysis focuses on the initial plumbing failure (i.e. the primary crack).

Figure #1: Photograph of the failed cold water supply line which is the focus of the plumbing failure analysis. It is a corrugated line made from chrome plated yellow brass (65% Cu/ 35% Zn).

Procedure

The pipe failure analysis was performed by visual and with a microscopic analysis. In addition, the pipe failure was cross-sectioned and again viewed with a microscope.

Results

The figures below summarize the physical findings of the failure analysis.

Mag. 10X Mag. 30X

Figure #2: Photomicrographs of the primary crack. It appears to have formed at a “kink” in the tubing created during installation. In addition, the fracture surface shows areas of Zn depletion. It appears that the tube had been straightened during or after removal. There is a continuation of the primary crack shown in the upper right photomicrograph. This crack extension shows how brittle the pipe is in the region of the primary crack. Note also the white Zn rich corrosion deposits associated with the corrosion failure.

Mag. 10X Mag. 200X

Figure #3: Photomicrographs of the failed pipe after cross-sectioning. The cross-sectioning exposes the crack region. Associated with the cracking is a change in color of the brass. There are Zn depleted regions, and this indicates localized brass dezincification associated with the cracking. The higher magnification photo on the right shows a distinct color change of the brass. In addition, there is also porosity associated with the Zn depletion of the brass near the failure.

Mag. 10X Mag. 40X

Figure #4: Photomicrographs of another crack located where the ferrule is deforming the tube at one end. This crack also has brass dezincification associated with it.

Discussion

The cracking appears to be the result of stress corrosion cracking. There is residual stress as a result of plastic deformation of the corrugated yellow brass tubing during installation. The metal corrosion also appears to be associated with the absence of the chrome plating. In addition, there is brass dezincification as a result of the stress corrosion cracking. Possibly, ammonia containing cleaners had been used on or near this supply line, and this contributed to the corrosion.

Conclusion

The plumbing failure analysis indicates that the failure was a result of stress corrosion cracking and dezincification of yellow brass. This failure is appears to be localized season cracking of brass.

Filed Under: White Papers

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Read Consulting Failure Analysis

Thomas L. Read, PhD,
1435 Fulton Road Santa Rosa, CA
Phone: 707-494-5089
email: info@readconsulting.com

  • Home
  • About
  • Experience
  • Expertise
  • Laboratory
  • Failure Analysis
  • Blog
  • White Papers

Read Consulting Failure Analysis

Thomas L. Read, PhD,
1435 Fulton Road Santa Rosa, CA
Phone: 707-494-5089
email: info@readconsulting.com

Connect With Read Consulting

FacebookTwitterLinkedinYouTubeRSS Feed

Registered Professional Engineer

Thomas L. Read, PhD., CEO
Registered Professional Engineer
Certificate No. MF002174
State of California.

Copyright © 2025 Read Consulting · Materials Failure Analysis And Process Engineering